THERMASOLV CF1

  • Dielectric heat transfer fluid
  • Boiling point: 170°C / 338°F
  • High critical temperature
THERMASOLV CF1

THERMASOLV CF1 is a dielectric heat transfer fluid, dedicated for 1-phase immersion or direct cooling systems. Its high electrical insulation properties allows to immerse electronics & electrical devices under power in the fluid.

The favorable characteristics of the product’s viscosity, density and surface tension allows optimal surface contact, which contributes to a superior heat transfer performance.
Its very good compatibility with all metals, a wide range of plastics & elastomers and the chemical stability of the fluid, makes THERMASOLV CF1 an ideal fluid for immersion cooling.

THERMASOLV CF1 is formulated with safety in mind. It is non-toxic, has no mentioning of any EUH-phrases, is non-flammable and has no flash point.

This is not a product

Although fully in line with safety & environmental regulations, this product doesn`t match our strict criteria to be labelled as a Greenway product.

LOOKING FOR A MORE SUSTAINABLE SOLUTION?

GREENWAY ALTERNATIVE

  • We currently don`t have a Greenway alternative but our target is to develop one in the near future. In case you want us to prioritize the development of a Greenway alternative, do not hesitate to contact us.
Discover more about Greenway

Benefits

Performance

  • Excellent thermal conductivity
  • Very low surface tension
  • High electrical insulation
  • Low kinetic viscosity & low freezing point limit the load on pumps

Cost

  • Thermally and chemically stable in use
  • Can be returned for recycling and re-use
  • No flash point: does not require the use of explosion proof equipment

HSE

  • No Ozon Depletion Potential
  • Non-flammable

Process examples

The best process will depend on factors such as operating conditions & equipment. Our team is ready to advise you. Although this product has very good compatibility properties, we cannot foresee all materials that could be exposed to the fluid. We strongly recommend testing before use.

Processes

The product can be used in the following processes:

  • Immersion cooling (only 1-phase)
  • Direct cooling, where the fluid flows through cold plates or tubes (only 1-Phase)
  • Specific manufacturing processes which need stable and uniform cooling
  • Dielectric testing

Temperature limits

1-phase system

  • Recommended Temperature Minimum: -100°C / -148°F
  • Recommended Temperature Maximal: 160°C / 320°F